KEY FEATURES
-
Quick Installation
-
Strong Stability
-
High Safety
Product Display
Product Model and Data-Sheets
- Battery Performance
-
Battery Type
LFP (LiFePO4)
-
Nominal Voltage (V)
51.2
-
Nominal Capacity (Ah)
100 * 3
-
Nominal Energy (kWh)
15.36
-
Voltage Range (V)
43.2 ~ 58
-
Charge Cut-off Voltage
Overall voltage≥58V or single≥3.63V
-
Discharge Cut-off Voltage
Overall voltage≤43.2V or single≤2.7V
-
Maximum Charge Current (A)
50 * 3
-
Maximum Discharge Current (A)
100 * 3
-
CELL Cycle Life
25±2℃, 1C, 80%EOL ≥3000
- General Parameters
-
Thermal Management
Natural Cooling
-
Recommend Depth of Discharge
90%
-
Charge Temperature Range (℃)
2 ~ 53
-
Discharge Temperature Range (℃)
-18 ~ +53
-
Storage Temperature Range (℃)
-20 ~ +35
-
Maximum Working Altitude (m)
< 2000
-
Dimensions [W x L x H] (mm)
550 x 207 x 1328(±3)
-
Battery Pack Weight (kg)
174 ± 5
-
IP Rating
IP65
-
Communication Port
CAN / RS485
-
Certification Standard
CE / IEC 62619 / UN38.3
- Battery Performance
-
Battery Type
LFP (LiFePO4)
-
Nominal Voltage (V)
51.2
-
Nominal Capacity (Ah)
100 * 2
-
Nominal Energy (kWh)
10.24
-
Voltage Range (V)
43.2 ~ 58
-
Charge Cut-off Voltage
Overall voltage≥58V or single≥3.63V
-
Discharge Cut-off Voltage
Overall voltage≤43.2V or single≤2.7V
-
Maximum Charge Current (A)
50 * 2
-
Maximum Discharge Current (A)
100 * 2
-
CELL Cycle Life
25±2℃, 1C, 80%EOL ≥3000
- General Parameters
-
Thermal Management
Natural Cooling
-
Recommend Depth of Discharge
90%
-
Charge Temperature Range (℃)
2 ~ 53
-
Discharge Temperature Range (℃)
-18 ~ +53
-
Storage Temperature Range (℃)
-20 ~ +35
-
Maximum Working Altitude (m)
< 2000
-
Dimensions [W x L x H] (mm)
550 x 207 x 927(±3)
-
Battery Pack Weight (kg)
119 ± 5
-
IP Rating
IP65
-
Communication Port
CAN / RS485
-
Certification Standard
CE / IEC 62619 / UN38.3
- Battery Performance
-
Battery Type
LFP (LiFePO4)
-
Nominal Voltage (V)
51.2
-
Nominal Capacity (Ah)
100
-
Nominal Energy (kWh)
5.12
-
Voltage Range (V)
43.2 ~ 58
-
Charge Cut-off Voltage
Overall voltage≥58V or single≥3.63V
-
Discharge Cut-off Voltage
Overall voltage≤43.2V or single≤2.7V
-
Maximum Charge Current (A)
50
-
Maximum Discharge Current (A)
100
-
CELL Cycle Life
25±2℃, 1C, 80%EOL ≥3000
- General Parameters
-
Thermal Management
Natural Cooling
-
Recommend Depth of Discharge
90%
-
Charge Temperature Range (℃)
2 ~ 53
-
Discharge Temperature Range (℃)
-18 ~ +53
-
Storage Temperature Range (℃)
-20 ~ +35
-
Maximum Working Altitude (m)
< 2000
-
Dimensions [W x L x H] (mm)
550 x 207 x 526(±3)
-
Battery Pack Weight (kg)
64 ± 5
-
IP Rating
IP65
-
Communication Port
CAN / RS485
-
Certification Standard
CE / IEC 62619 / UN38.3